Gaalflex®

TRAY 1002

Special PVC oil resistant, flexible tray cable, Machine-Tool cable, acc. to UL 1277 (TC-ER) DIR BUR OIL RES I 600 V 90°C Dry / 75°C Wet FT4 or UL 1277 FLEXIBLE MOTOR SUPPLY CABLE 1000 V 90°C Dry and UL 2277 WTTC 1000 V 90°C Dry or UL 1063 MTW “FLEXING” or AWM 21179 c(UL) CONTROL CABLE CIC/TC PVC FT4 or AWM I/II A/B 90°C 1000 V FT1

Construction

CONDUCTOR

FLEXIBLE RED COPPER CONDUCTOR CL. 5,
ACC. TO IEC 60228, DIN VDE 0295 AND UL STANDARD 83 FROM 18 TO 16 AWG:
CORES TYPE TFF
FROM 14 AWG AND OVER:
CORES TYPE THHW

INSULATION

GAALTHERM® 522

COLOUR CORES

BLACK CORES WITH CONSECUTIVE NUMBERS ACC. TO EN 50334, GREEN-YELLOW FROM 3 CORES

STRANDING

IN LAYERS

OUTER SHEATH

BLACK (RAL 9005), SPECIAL PVC OIL RESISTANT COMPOUND
ACC. TO UL 1277 AND UL 1063

Features

  • AWM STYLE 10012/21179 90°C 600 or 1000 V
    C(UL) CONTROL CABLE CIC/TC PVC FT4,
    CSA AWM I/II A/B 90°C 1000 V FT1
  • ACC. TO UL 1063 UL(MTW) “FLEXING” AND UL 1277 (TC-ER)
    DIR BUR OIL RES I 600 V 90°C DRY / 75°C WET FT4
  • ACC. TO UL 2277: FLEXIBLE MOTOR SUPPLY LEAD CABLE
    AND WIND TURBINE TRAY CABLE (WTTC) 1000 V 90°C DRY
  • ACC. TO NFPA 79 2007 AND NEC 336.10(7)
    CLASS 1 DIV. 2 ART 336, 392, 501
  • DIRECT BURlAL ACC. TO UL 1277 PSRT. 5.2. (WET LOCATION INSULATIONS)
    AND 18.1 – 18.6 (CRUSHING TEST)
  • OUTDOOR USE
  • EXPOSED RUNS
  • CABLE FOR TRAY USE
  • OIL RESISTANCE
  • WATER RESISTANCE
  • RoHS AND CE APPROVAL

Resistance

FIRE PERFORMANCE ACC. TO

(UL) FT4/IEEE, UL 1685

OIL RESISTANCE ACC. TO

TO UL OIL RES I

UV RESISTANT / SUNLIGHT RESISTANT ACC. TO

ACC. TO EN 50396 AND HD 605 A1, UL 1581

Technical data

NOMINAL VOLTAGE :

UL-TC/MTW

600 V

NOMINAL VOLTAGE :

IEC / UL-AWM

1000 V

TEST VOLTAGE :

4kV

TEMPERATURE RANGE :

FIXED LAYING

FLEXIBLE APPLICATION

 

-40°C UP TO +90°C
(UL-AWM UP TO +105°C)

-5°C UP TO +90°C (UL-AWM UP TO +105°C)

MIN. BENDING RADIUS :

FIXED LAYING

FLEXIBLE INSTALLATION

 

4 x D

13 x D